Products

KLEA®32

Trademark:KLEA


Introduction:
Of interest as both a blend component for alternatives to R-22 and R-502 such as KLEA®407A and KLEA®410A, also as an attractive low GWP candidate for air conditioning. It can be blended with HFO’s to improve performance.
Please note that not all products are available in all markets.

⇒KLEA®32 SDS Download

KLEA®32 Physical Properties
Property S.I.Units British Units
Boiling Point -51.7 (°C @ 1 atm) -61.0 (°F @ 14.7 psia)
Vapour Pressure 16.9 (bara @ 25°C) 220.6 (psia @ 70°F)
Critical Temperature 78.35 (°C) 173.0 (°F)
Critical Pressure 57.16 (bara) 829.04 (psia)
Latent Heat Vaporisation 270.22 (kJ/kg @25°C) 116.2 (Btu/lb @ 77°F)
Coeff. Vol. Therm. Exp

0.003630 (K-1 0-20°C)

0.002148 (°F-1 40-80F)

Saturated Vapour Density

2.98 (kg/m3@nBpt)

0.186 (lb/cuft @nBpt)

KLEA®32 Specification
TEST ITEMS ACCEPTANCE VALUES
Appearance Clear colourless liquefied gas
Purity (% by Weight) 99.9 minimum
Volatile impurities, including other refrigerants
(% by weight )
0.1 maximum
R31  (ppm by weight) 5 maximum
Water content (ppm by weight) 10 maximum
Evaporation residue (ppm by weight) 10 maximum
Halide Pass (No visible turbidity, usually Chloride <3ppm)
Non-absorbable gases
(% by volume in vapor phase)
1.5 maximum
Acidity (ppm by weight as HCl) 1.0 maximum
Particulates / Solids Visually clean to pass
R12  (ppm by weight) 200maximum
R21  (ppm by weight) 200maximum
R22  (ppm by weight) 200maximum
R23  (ppm by weight) 200maximum
R40  (ppm by weight) 200maximum